APPLICABLE PUBLICATIONS
-
Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only.
-
American National Standards Institute (ANSI):
C37.57-10...............Metal-Enclosed Interrupter Switchgear
Assemblies - Conformance Testing
C37.58-10...............Indoor AC Medium-Voltage Switches for Use in
Metal-Enclosed Switchgear - Conformance Test Procedures
-
International Code Council (ICC):
IBC-12..................International Building Code
-
Institute of Electrical and Electronics Engineers (IEEE): C37.20.3-01.............Metal-Enclosed Interrupter Switchgear
C37.47-11...............High Voltage (>1000V) Current-Limiting Type
Distribution Class Fuses and Fuse Disconnecting Switches
C37.48-05...............Guide for Application, Operation and
Maintenance of High Voltage Fuses, Distribution Enclosed Single Pole Air Switches, Fuse Disconnecting Switches, and Accessories
-
National Electrical Manufacturers Association (NEMA):
C37.22-97...............Preferred Ratings and Related Required
Capabilities for Indoor AC Medium-Voltage Switches Used in Metal-Enclosed Switchgear
-
National Fire Protection Association (NFPA):
70-11...................National Electrical Code (NEC)
PART 2 - PRODUCTS
-
MEDIUM-VOLTAGE SECTIONALIZING SWITCHES
-
Shall be in accordance with ANSI, IEEE, NEMA, NFPA, as shown on the drawings, and have the following features:
-
304 stainless steel hardware.
-
Silicon bronze penta-head bolt standards on all models.
-
Light grey mounting bars for high visibility in adverse weather.
-
All-welded construction.
-
Ground nuts located on mounting bar and on the enclosure for concentric neutral.
-
Fiberglass ground sleeves for additional cable training.
-
Wind stop for top-hinged units.
-
Munsell Greenn (7GY 3.29/1.5) finish. Six-stage power wash with iron phosphate durable power paint.
-
12ga steel construction.
-
Park stand quantities as shown on the plans.
MEDIUM-VOLTAGE SECTIONALIZING SWITCH METAL GROUND SLEEVE PAD
-
Shall be in accordance with ANSI, IEEE, NEMA, NFPA, as shown on the drawings, and have the following features:
-
304 stainless steel hardware.
-
14ga steel construction.
MEDIUM-VOLTAGE SECTIONALIZING SWITCH LOADBREAK APPARATUS CONNECTOR
-
Shall be in accordance with ANSI, IEEE, NEMA, NFPA, as shown on the drawings, and have the following features:
-
200A, 15kV Class loadbreak junction interfaces that are internally bused together and meet all requirements of IEEE Standard 386 – Separable Insulated Connecter Systems. Quantity as shown on plans.
-
Continuous solid current path of all copper alloy. Aluminum components shall not be used.
-
Body shall be molded of high quality peroxide-cured EPDM insulation and a molded on peroxide-cured semi-conductive EPDM shield.
-
Provide yellow latch indicator ring.
-
The loadbreak junction shall have an adjustable stainless steel bracket for mounting at various operating angles on flat or curved surfaces, with up to 90degree tilt in 10degree increments.
-
No special tools shall be required. Junction shall be bolted to the mounting surface.
PART 3 - EXECUTION
-
INSTALLATION
-
Install switches in accordance with the NEC, manufacturer's instructions and recommendations, and as shown on the drawings.
-
Anchor switches with rustproof bolts, nuts, and washers not less than
13 mm (1/2 inch) diameter, in accordance with manufacturer’s instructions, and as shown on drawings.
-
Exterior Location: Mount switches on metal ground sleeve pad as manufactured by Maysteel CW300 Series.
ACCEPTANCE CHECKS AND TESTS
-
Perform in accordance with the manufacturer's recommendations. In addition, include the following:
-
Visual Inspection and Tests:
-
Compare switches nameplate data with specifications and approved shop drawings.
-
Inspect physical and mechanical condition.
-
Confirm correct application of manufacturer's recommended lubricants.
-
Vacuum-clean switch enclosure interior. Clean switch enclosure
exterior.
-
Verify appropriate anchorage and required area clearances.
-
Verify appropriate equipment grounding.
-
Inspect all field-installed bolted electrical connections, verifying tightness of accessible bolted electrical connections by calibrated torque-wrench method, or performing thermographic survey after energization under load.
-
Exercise all active components.
Dostları ilə paylaş: |