075322 Milled timber cladding
Milled timber cladding shall comply with the requirements of Specification 075313.
075323 Asbestos cement sheets external Soffits.
Comply with Specification 075313 for suspended Soffits.
Flat asbestos not less than 4mm thick complying with Specification 062432 shall be used for external Soffits.
Asbestos Soffits shall be nailed to sawn timber battens.
Unless shown on detail drawings, the battens shall not be less than 40x50mm, spaced at maximum intervals of 600mm in both directions. The battens shall be securely fixed to truss members as in Specification 075312. Corners where Soffits join with walls shall be covered in molded timber corner lists, not less than 50mm wide.