15226 Conduits for Internal Wire Drawing

All metal conduits shall be heavy duty galvanized and shall be laid in straight and symmetrical lines. The ends of all conduits shall be carefully reamed to remove all burrs and sharp edges after the screw threads have been cut. The ends of the conduits shall be butt welded solidly in all couplings, and where conduits terminate in switch fuses, fuse boards, adaptable boxes etc., they shall be connected thereto by means of smooth bore male brass brushes, compression washers and sockets. All bends shall be made on site to suit site conditions and not more than two right angle bends shall be permitted without the interposition of a draw box. No tees, elbows or bends either solid or inspection will be permitted, unless specifically mentioned in the specification or in the drawings.

All PVC conduits shall be of high impact PVC type. Ends shall be carefully trimmed of all burrs. Joints shall be made using adhesive supplied by the conduit manufacturer.