BaTCoDA

MOUNTING HEIGHTS
Except where otherwise detailed in the drawings or stated in the Bill of Quantities all accessories and fittings shall be fixed at the following heights above finished floor level: -


  • Distribution boards 1700mm to centerline of board

  • Lighting switches and push buttons 1400mm.

  • Lighting switches and push buttons above beds 1000mm.

  • Sockets (general) 300mm.

  • Sockets on or above benches 1500mm above bench top

  • Sockets in Workshops 1100mm.

  • Telephone outlets 300mm.

  • Bells 2100mm


1522 UNDERGROUND CABLE DUCTS

15221 General

Underground cable ducts for incoming power supply cables and telephone service cables to the buildings, shall be supplied and installed by the Contractor. It shall be the responsibility of the Contractor to ensure that the underground duct is installed correctly according to each party’s requirements; and to the purpose. The Contractor shall liaise closely with EELPA and ETA to ensure that their requirements fully satisfied. It shall be the Contractor's responsibility to ensure that adequate information concerning easy bends, directions of runs, etc. is given before work commences.