MATERIALS


  1. Spray Applied Polyurethane Foam Insulation system in accordance with CAN/ULC S705.1-05 TYPE 2 (Including amendments 1 & 2) Standard for Thermal Insulation Spray Applied Rigid Polyurethane Foam, Medium Density, Material Specification and those specific objectives performances.

  2. Product: HEATLOK SOYA / POLARFOAM SOYA.

  3. The product shall be evaluated by the NRC for a minimum of 8 years.


    1. PHYSICAL TEST OBJECTIVE RESULT UNIT


PROPERTIES

  1. Density ASTM D1622 Min. 33 Kg/m3

  2. Thermal Resistance ASTM C518 180 days/230C Min. 1.17/25 mm RSI

6.6/1” R

  1. Long Term Thermal CAN/ULC S 770 Min. 1,05/25 mm RSI

Resistance (LTTR) CAN/ULC S705.1-Type 2 6./1” R


  1. Dimensional stability ASTM D 2126 (% of change in volume at 28 days)

-200C Min. -0.03 %

700C R.H. >97±3 % Max. + 9.8 %

800C Max. + 2.9 %


  1. Flames spread Index CAN/ULC S 102-03 Max. 200 FSI

  2. Smoke Develop Index CAN/ULC S 102-03 Max. 396 SDI

  3. Compressive strength ASTM D1621 Min. 195 KPa

  4. Tensile strength ASTM D1623 Min. 335 KPa

  5. Open cells ASTM D2856 Min. <1 %

  6. Water absorption ASTM D2842 (96 hrs) Max. 0.8 %

  7. Air barrier Material at CCMC 07273 (25 mm core Max. 0.00004 L/s.m2 at 75 Pa

75 Pa only)

  1. Fungi Resistance ASTM C 1338 Min. No Fungal Growth

  2. V.O.C. CAN/ULC S 774 Max. 1 Day

  3. V.O.C., GREENGUARD Min. Gold Certification

  4. Water vapour permeance

50mm core product only ASTM E96 Max. 37 Ng/Pa s m2

Note : When the spray applied polyurethane foam is used as the design vapour barrier, use points 15, 16 or 17.

  1. Water vapour permeance assembly: spray foam applied on concrete

75mm on concrete ASTM E96 (system) Max. 8 Ng/Pa s m2

  1. Water vapour permeance assembly: spray foam applied on gypse

75mm on gypse ASTM E96 (system) Max. 29 Ng/Pa s m2

  1. Water vapour permeance assembly: spray foam applied on plywood

75mm on plywood ASTM E96 (system) Max. 21 Ng/Pa s m2

Note : When the building has more than 3 stories and the exterior finish is not mansonry or concrete, the assemblies shall meet art 3.2.3.8 of NBC, use point 18.

  1. Specific fire wall assembly CAN/ULC S 101 Min. 15 min. resistance test

  2. Application temperature Min. - 20

  3. Reference product HEATLOK SOYA / POLARFOAM SOYA




    1. PRIMERS

  1. Use primers as per manufacturer recommendations and CAN / ULC-S705.2 for surface conditions.

  1. For oily metal surface like Z-Bar, steel deck roof or curtain wall pan, aluminium tube, and PVC, applied ADBOND 8388-1 adhesive primer, colour: red before spraying polyurethane foam.


2.5 EQUIPMENT

Equipment shall be as recommended in CAN/ULC-S705.2 and approved by foam manufacturer for type of application.



PART 3-EXECUTION

Note: Check the adhesion and compatibility with: flashing, membranes, coatings, and respect DEMILEC typical details drawing.
3.1 EXAMINATION

  1. Verify that surfaces and conditions are suitable to accept work as outlined in this section.

  2. According to the prescriptions of the standard CAN/ULC-S705.2, verify the conditions of surfaces.

  1. Surfaces to be covered with spray foam shall be free of an excess of moisture, frost, oil, rust, and any other foreign material able to have a negative affect on the adhesion of the product.

  2. Make sure of the complete cure of the substrates: concrete, mortar, fillers, membranes, primers, coatings or other surfaces, before pulverizing, taking into account climatic conditions.

  3. If the thickness of application is greater than 50 mm, detail membrane around opening need to be made in accordance to DEMILEC typical details. Drawing are available on www.demilec.com or contact your representative. Option use mechanical fastener to secure self-adhesive membranes around openings only (galvanized steel angle: 13 mm x 25 mm x 0.42 mm in thickness (gypsum corner bead). Fixed at 400 mm C/C. ALTERNATIVE: Follow

Note: Refer the mechanical fastener to the appropriate section (07 27 00) for coordination.

  1. All oily metal surface like Z-Bar, steel deck roof or curtain wall pan, aluminium tube, and PVC, shall be primed as mentioned in CAN / ULC S705.2 art: A 1.7.


Note: See DEMILEC drawing. Refer that alternative to the appropriate section (07 42 00) for coordination.
B) If required, all spray applied membrane shall be installed before the “Z” bars.

  1. Respect the moisture content of the different building materials.

  2. In the case of particular conditions, follow the recommendations of the manufacturer.

  3. Report in writing any defects in surfaces or conditions that may adversely affect the performance of products installed under this section to the consultant before commencement of work.

  4. For occupied building application, confirm that all requirements in Article 1.11 are in place.

  5. Commencement of work outlined in this section shall be deemed as acceptance of existing work and conditions.


3.2 APPLICATION

  1. Spray application of polyurethane foam shall be performed in accordance with CAN/ULC-S705.2. Standard for Thermal Insulation Spray Applied Rigid Polyurethane Foam, Medium Density, Installer’s Responsibilities.

  2. Apply only when surfaces and environmental conditions are above -20 C. Refer to technical data sheets.

  3. Apply in consecutive passes (min. 15 mm, max. 50 mm) to obtain the thickness as indicated on drawings, or ( mm) for wall, ( mm) for roof to achieve the required thermal insulation value. Use only the Long Term Thermal Resistance (LTTR) CAN/ULC S 770 test method to calculated design R value.

  4. Do not spray closer than 3” (75 mm) of chimneys, recess spotlight or other source of heat.


3.3 TOLERANCE

  1. Apply the product to achieve an average thickness of ± 6 mm (1/4”), from (9 readings in 1 M2), of the thickness requirements in the drawings at a minimum of 1 M2 readings for each 150 m2 surface sprayed.

  2. Apply the insulation uniform in accordance to NBC article 9.25.2.3. 1).


3.4 FIRE PROTECTION

  1. Any open flame or welding that is not allowed to be in contact with the Spray Polyurethane Foam in place. Use protection as required in CAN / ULC S705.2.

  2. All plastic insulation must be protected from interior occupancy space by an approved thermal barrier to meet the requirements of local Building Codes (See section 07 81 16).

Note: Work related to thermal barrier installation should be specified under appropriate sections.
----------------------------------END OF THE SECTION-----------------------------------------------