Observe safety lifesavers distribution commissioning work instruction


SERVICE ADDRESS (house or lot no. and road name)



Yüklə 60,34 Kb.
səhifə2/2
tarix05.01.2022
ölçüsü60,34 Kb.
#64300
1   2
1. SERVICE ADDRESS (house or lot no. and road name)






2. CABLE

Size of conductor mm²

Length of cable (approximately) m

Pillar size

Mini

Uni

Work Package No.




3. PREPARATION

1

Check pillar on the right alignment. Refer to drawings U8, U9, and U19/3 of Distribution Construction Standards Handbook HB01.




2

Check all connections at the service pillar and check for tightness.




3

Separate the earth conductor from the neutral terminal block at the pillar.




4

Check the service cable and conduit to the pole in its final position.




5

Separate the service cable cores at the pole-top for testing.




6

At the pillar, conduct an insulation test on the service cable and record the results.




Use a 1kV insulation resistance tester for one minute between phase-to-phase and phase-to-neutral.

Values must be greater than 10M.



Ensure that all persons are clear of the circuit before testing.

Red – white

MΩ

White – blue

MΩ

Blue– red

MΩ

Red – neutral

MΩ

White – neutral

MΩ

Blue – neutral

MΩ

7

Perform a sheath integrity test on the service cable and record the results.




  1. Disconnect all neutral/screen connections of the cable that is to be tested.

  2. Use a 1kV insulation resistance tester and test for one minute between all the neutrals/screens and an effective earthed reference point (i.e. rod) embedded in the ground more than 2m from any electrically conductive object.

Values must be:

  • greater than 10MΩ for new cables

  • greater than 1MΩ for old cables

  1. Reconnect all the neutral/screen connections.

Neutral – earth

MΩ




4. COMMISSIONING

Note: A high impedance voltmeter may give a high voltage reading on an unconnected phase when one phase is energised.
If voltage above 6V exists on items 3, 6, 7, 10 and 13, stop immediately and commence a fault-finding procedure.

1

Prove the test equipment (voltmeter) is functioning correctly.




2

Identify neutral and fit a neutral tag (HG 2101) to the aerial mains neutral conductor and the service cable neutral conductor.




3

Test between the aerial mains neutral conductor and the service cable neutral conductor.

Value < 6V

Volts

4

Connect the service cable neutral conductor to the aerial mains neutral conductor and check for tightness.




5

Conduct a service connection test on all installations where the service connections have been disturbed.




6

Test between the pillar earth electrode and the neutral terminal block at the pillar.

Value < 6V

Volts

7

Test between the neutral terminal block at the pillar to the red, white and blue terminals block at the pillar.

Value < 6V

Volts




8

Connect the blue-phase service conductor to the blue-phase aerial mains conductor and check for tightness.




9

Test between the pillar earth electrode and the blue terminal block at the pillar.

Value 216–253V

Volts

10

Test between the neutral terminal block at the pillar to the red and white terminal block at the pillar.

Value < 6.0V

Volts

11

Connect the white-phase service conductor to the white-phase aerial mains conductor and check for tightness.




12

Test between the pillar earth electrode and the white terminal block at the pillar.

Value 216–253V

Volts

13

Test between the neutral terminal block at the pillar to the red terminal block at the pillar.

Value < 6.0V

Volts

14

Connect the red-phase service conductor to the red-phase aerial mains conductor and check for tightness.




15

Test between the pillar earth electrode and the red terminal block at the pillar.

Value 216–253V

Volts

16

Reconnect the earth conductor to the neutral terminal block at the pillar and check for tightness.




17

Test between the neutral terminal at the pillar and the following:

Red terminal at the pillar

Value 216–253V

Volts

White terminal at the pillar

Value 216–253V

Volts

Blue terminal at the pillar

Value 216–253V

Volts

18

Test between the red, white and blue terminals at the pillar.

Red to white terminal at the pillar

Value 376–440V

Volts

White to blue terminal at the pillar

Value 376–440V

Volts

Blue to red terminal at the pillar

Value 376–440V

Volts

19

Conduct a phase sequence test to prove correct phase rotation.

Ǿ #

Ǿ #

Ǿ #




5. HANDOVER OF RESPONSIBILITY

The commissioning officer must ensure that checks are completed and test results comply with the minimum standards.



I hereby certify that all items have been completed with satisfactory results and transfer control to the project manager.

Commissioning officer: NAC#:



Signature: Date & time:




  1. Ensure the work area is left tidy with no hazards to the public.

  2. Hand over responsibility to the operating authority.

  3. Return this form to the project file as a record of the commissioning/handover certificate.

  4. After the on-site project officer signs off on the DCWI, send a scanned copy to the relevant manager:

  • the construction manager (for work performed by Western Power employees)

or

  • the service manager (for contractors).




Network Standard 11/2013 DM# 6356290 of

Yüklə 60,34 Kb.

Dostları ilə paylaş:
1   2




Verilənlər bazası müəlliflik hüququ ilə müdafiə olunur ©muhaz.org 2024
rəhbərliyinə müraciət

gir | qeydiyyatdan keç
    Ana səhifə


yükləyin